A technical article published by EEPower describes a smart distribution transformer architecture combining condition monitoring, active voltage compensation and AMI communication. Prototype testing demonstrated voltage regulation from 212 V AC to 220 V AC under a 25.6 kW load.
The design pairs a conventional distribution transformer with a power electronic compensator that processes only the power associated with the voltage deviation. According to the study, this approach can reduce the required converter rating and associated losses while retaining the transformer’s original power-transfer function.
The compensator uses two single-phase full-bridge converters in a back-to-back topology. A single controller coordinates the series and shunt converters to compensate for feeder voltage deviations.
Two monitoring configurations are proposed. An external Transformer Terminal Unit supports existing transformers, collecting voltage, current and terminal temperature measurements. A Transformer Smart Unit for new transformers adds insulating oil temperature and oil-level monitoring.
The communication system follows Taiwan Power Company’s low-voltage AMI specifications. Transformer measurements are transmitted through a DLMS server and data concentrator to a backend platform for storage, display and abnormal-condition alerts.
The platform is designed to combine operating data with feeder information, supporting equipment location identification and maintenance planning.
The reported experiment confirms voltage compensation under the specified load and input-voltage conditions. The supplied results do not establish performance across other operating conditions or in field deployment.
Source: EE Power